產品分類
聯系方式
|
|
您當前的位置: 首頁 » 供應產品 » LGK16系列燃氣燃燒器控制器
程控器及底座 >> 西門子程控器(SIEMENS) >> LGK16系列燃氣燃燒器控制器(SIEMENS)
|
|
|
LGK16系列燃氣燃燒器控制器
品牌:SIEMENS(西門子)
產地:德國
|
產品介紹
|
Burner controls type LGK16... feature a self-checking flame supervision circuit. That supervision circuit initiates the required safety actions not only in the case of premature or missing flame signals, but also in the event of any kind of fault on the flame detector, the detector cables or the flame signal amplifier that could simulate a flame signal during burner operation.
The burner controls are therefore suited for use in all types of oil- or gas-fired combustion plants where self-checking flame supervision systems are either mandatory or recommendable:
-
Burners that operate continuously
-
Burners in intermittent operation that, in the case of great heat demand, may operate continuously for more than 14 hours, e.g. in plants using boiler sequencing
-
-
Burners in plants where, for specific safety requirements, supervision of the burner by a self-checking flame supervision system seems advisable
|
型號表
|
|
LGK16.122A27
|
LGK16.133A27
|
LGK16.322A27
|
LGK16.333A27
|
LGK16.335A27
|
LGK16.622A27
|
LGK16.635A27
|
注釋
|
t1
|
10
|
9
|
36
|
31.5
|
37.5
|
66
|
37.5
|
預吹掃時間(風門全開時)
|
TSA
|
2
|
3
|
2
|
3
|
2.5
|
2
|
2.5
|
安全時間
|
TSA’
|
-
|
-
|
-
|
-
|
2.5
|
2
|
2.5
|
安全時間
|
t3
|
4
|
3
|
4
|
6
|
5
|
4
|
5
|
預點火時間
|
t3’
|
-
|
-
|
-
|
-
|
2.5
|
-
|
2.5
|
長預點火時間
|
t3n
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
后點火時間(點火變壓器連接端口15)
|
t4
|
6
|
6
|
10
|
12
|
12.5
|
10
|
12.5
|
從TSA開始到端口19的閥打開的間隔時間
|
t4’
|
-
|
-
|
-
|
-
|
15
|
-
|
15
|
從TSA開始到端口19的閥打開的間隔時間
|
t5
|
4
|
3
|
10
|
12
|
12.5
|
10
|
12.5
|
從t4結束到比例調節或端口20的閥門打開的間隔時間
|
t6
|
10
|
14.5
|
12
|
18
|
15
|
12
|
15
|
后吹掃時間
|
t7
|
2
|
3
|
2
|
3
|
2.5
|
2
|
2.5
|
打開風機馬達2的延遲時間
|
t8
|
30
|
29
|
66
|
72
|
75
|
96
|
105
|
沒有t11和t12時,整個啟動階段時間
|
t9
|
2
|
3
|
2
|
3
|
5
|
2
|
5
|
第二安全時間
|
t10
|
6
|
6
|
8
|
12
|
10
|
8
|
10
|
從啟動到空氣壓力監測開始工作的間隔時間
|
t11
|
Optional
|
風門打開到大位置的時間
|
t12
|
Optional
|
風門至小火位置的時間
|
t16
|
4
|
3
|
4
|
6
|
5
|
4
|
5
|
從啟動到風門打開命令的間隔時間
|
t20
|
32
|
60
|
-
|
27
|
22.5
|
-
|
-
|
鎖定后程序內部循環時間
|
類似型號
|
LFL1.122
|
LFL1.133
|
LFL1.322
|
LFL1.333
|
LFL1.335
|
LFL1.622
|
LFL1.635
|
|
|
|
|
免責聲明:(1)以上所展示的信息由企業自行提供,內容的真實性、準確性和合法性由發布企業負責,環球塑化網對此不承擔任何保證責任。我們原則上建議您優先選擇“塑企通”會員合作! (2)同時我們鄭重提醒各位買/賣家,交易前請詳細核實對方身份,切勿隨意打款或發貨,謹防上當受騙。如發現虛假信息,請向環球塑化網舉報。
|